Click to Enlarge |
Phoenix Controls healthcare systems provide immediate room
conversions that contain highly contagious disease and assure the integrity of
surrounding spaces and their occupants. Activated by either the BMS or a local wall
switch mounted external to the room; Theris Pandemic Mode overrides normal
control to achieve negative room pressure, drive return valves to shutoff,
increase exhaust, and command supply to a predetermined setting including
shutoff. Environmental settings for heating, cooling, auxiliary control,
humidity, and other parameters can also be configured and activated when the
room converts. If an APM2 is wired into the room, a status banner can be
displayed on-screen and an audible alarm sounded to alert healthcare staff and
provide live data for pressure, ACH, temperature, and humidity.
Once
the crisis is past, on command the room can be seamlessly moved to
decontamination mode, then reverted to use without down time or lengthy
transitions.